Lighting layout calculator
Number of fixtures and a grid layout for a room by the lumen method, from the target lux for the space type, fixture lumens, utilization and light loss.
Your job
Desk height is 0.8 m; use 0 for floor-level tasks.
Used only for the custom fixture.
Typically 0.55 to 0.75; lower in tall, narrow rooms.
LED in a clean space: 0.8 to 0.9.
Answer
- Fixtures
- 20 (5 x 4 grid)
- Spacing
- 2.4 m x 2 m, 1.2 m / 1 m to the walls
- Target and achieved
- 500 lux target, 525 lux maintained
- Fixtures from the formula
- 19.05 before rounding to a grid
- Connected load
- 800 W (8.3 W/m²)
- Room cavity ratio
- 2
Method: Lumen method: N = (E x A) / (lumens x CU x LLF); Target illuminance: IES Lighting Handbook recommended maintained illuminance by task (typical values; the NBC and NECB do not set lux); Compare the connected load with the applicable lighting-power requirements in the energy code adopted for the project; Check against the CEC edition and amendments your province adopts; confirm with the authority having jurisdiction.
Estimating aid based on a summary of the CEC. Provinces adopt different editions and amendments. Confirm with the authority having jurisdiction, and the engineer of record where one is involved.
Priced takeoff
- LED flat panel 2 x 4 ft$3,211.8020 ea at $160.5912 h
- Materials
- $3,211.80
- Labour, 12 h at $99.00
- $1,188.00
- Your cost, before markup and tax
- $4,399.80
Reference prices are dated baselines (2026-11) for Ontario. Confirm them with your supplier. In TradeQuote PRO your own saved prices replace these.
How it works
You enter 10 inputs. The calculator returns the quantities, rounds them up the way the material is sold, and lists the takeoff so it can be priced.
- Room length (m).
- Room width (m).
- Mounting height above the floor (m).
- Work plane height (m). Desk height is 0.8 m; use 0 for floor-level tasks.
- Space type.
- Target illuminance (0 = use the space type) (lux).
- Fixture.
- Custom fixture lumens (lm). Used only for the custom fixture.
- Coefficient of utilization. Typically 0.55 to 0.75; lower in tall, narrow rooms.
- Light loss factor. LED in a clean space: 0.8 to 0.9.
The method
- Lumen method: N = (E x A) / (lumens x CU x LLF)
- Target illuminance: IES Lighting Handbook recommended maintained illuminance by task (typical values; the NBC and NECB do not set lux)
- Compare the connected load with the applicable lighting-power requirements in the energy code adopted for the project
- Check against the CEC edition and amendments your province adopts; confirm with the authority having jurisdiction.
Check results against the code and manufacturer data that apply to your job. Prices are dated baselines to confirm with a supplier.
Add this to a real estimate in TradeQuote PRO
The takeoff lands as estimate lines with your prices, markup and tax, then becomes a proposal the client signs.
More electrical calculators
- Voltage drop calculatorVoltage drop in volts and per cent for copper or aluminum conductors, checked against the Canadian Electrical Code 3% and 5% limits, with the smallest size that passes.
- Conductor check (ampacity)Checks a conductor against a load: required ampacity with the continuous-load factor against the ampacity you read from your code book, corrected for ambient and conductor count, with pass or fail.
- Conduit fill calculatorConduit fill from the conductor and conduit diameters you enter, checked against the 53/31/40 per cent fill limits, with conduit, couplings, connectors and wire for the takeoff.
- Box fill calculatorAdds up the applicable box-fill allowances you enter for conductors, devices and clamps, and compares the total with the volume marked on the box.