Conductor check (ampacity)

Checks a conductor against a load: required ampacity with the continuous-load factor against the ampacity you read from your code book, corrected for ambient and conductor count, with pass or fail.

Your job

Sets the continuous-load factor: 80% of ampacity in a raceway or cable (100% if the equipment is marked for it); 70% of free-air ampacity (85% if marked for 100%).

Decides which continuous-load factor applies, and which ampacity table you read from your code book.

Read it from the code book ampacity table for your conductor material and installation, in the column for the conductor insulation temperature. Not supplied by this calculator. 0 means not entered yet.

Read it from the code book ambient correction table for your insulation and ambient temperature. Use 1 at the table base temperature.

Read it from the code book table for the number of conductors in the raceway or cable. Use 1 for three or fewer.

Defaults to 60 °C. Choose 75 °C only when the equipment is marked for 75 °C conductors. The conductor ampacity at this temperature limits the result.

The same code book table, read in the column for the termination temperature above. Leave at 0 if the ampacity typed above is already read at that column.

Only used to price the wire and for the small-conductor limit. It does not set any ampacity: the ampacity is the figure you typed from the code book.

Used with the length for the wire takeoff.

Leave at 0 for no takeoff.

Answer

Result
Enter the code book ampacity
Required ampacity
50 A (continuous load: 40 A at 80% of raceway or cable ampacity allowed)
Corrected available ampacity
n/a
Continuous factor used
0.8
Code book ampacity before correction
n/a
Termination limit
not entered
Smallest standard overcurrent device
50 A
  • Enter the conductor ampacity from your code book to get a pass or fail.

Method: Ampacity, ambient correction and derating figures are typed by the user from their own code book; this calculator does the arithmetic only; CEC Rule 8-104 continuous loads: 80% or 100% of ampacity in a raceway or cable, 70% or 85% of free-air ampacity (summary); CEC Rule 14-104 overcurrent protection of conductors, including the limits for small conductors (summary); Check against the CEC edition and amendments your province adopts; confirm with the authority having jurisdiction.

Estimating aid based on a summary of the CEC. Provinces adopt different editions and amendments. Confirm with the authority having jurisdiction, and the engineer of record where one is involved.

How it works

You enter 13 inputs. The calculator returns the quantities, rounds them up the way the material is sold, and lists the takeoff so it can be priced.

  • Load current (A).
  • Continuous load. A load that persists for more than 1 hour in any 2-hour period where the load is 225 A or less, or more than 3 hours in any 6-hour period above 225 A (CEC Rule 8-104). The conductor must then be sized with the continuous-load factor.
  • Equipment and overcurrent device rating for continuous loads. Sets the continuous-load factor: 80% of ampacity in a raceway or cable (100% if the equipment is marked for it); 70% of free-air ampacity (85% if marked for 100%).
  • Installation. Decides which continuous-load factor applies, and which ampacity table you read from your code book.
  • Conductor ampacity from the code book (A). Read it from the code book ampacity table for your conductor material and installation, in the column for the conductor insulation temperature. Not supplied by this calculator. 0 means not entered yet.
  • Ambient temperature correction factor. Read it from the code book ambient correction table for your insulation and ambient temperature. Use 1 at the table base temperature.
  • Derating factor for more than three conductors. Read it from the code book table for the number of conductors in the raceway or cable. Use 1 for three or fewer.
  • Termination temperature rating. Defaults to 60 °C. Choose 75 °C only when the equipment is marked for 75 °C conductors. The conductor ampacity at this temperature limits the result.
  • Ampacity at the termination temperature (optional) (A). The same code book table, read in the column for the termination temperature above. Leave at 0 if the ampacity typed above is already read at that column.
  • Conductor material for pricing.
  • Conductor size for pricing (optional). Only used to price the wire and for the small-conductor limit. It does not set any ampacity: the ampacity is the figure you typed from the code book.
  • Conductors to price. Used with the length for the wire takeoff.
  • Length to price (m). Leave at 0 for no takeoff.

The method

  • Ampacity, ambient correction and derating figures are typed by the user from their own code book; this calculator does the arithmetic only
  • CEC Rule 8-104 continuous loads: 80% or 100% of ampacity in a raceway or cable, 70% or 85% of free-air ampacity (summary)
  • CEC Rule 14-104 overcurrent protection of conductors, including the limits for small conductors (summary)
  • Check against the CEC edition and amendments your province adopts; confirm with the authority having jurisdiction.

Check results against the code and manufacturer data that apply to your job. Prices are dated baselines to confirm with a supplier.

Add this to a real estimate in TradeQuote PRO

The takeoff lands as estimate lines with your prices, markup and tax, then becomes a proposal the client signs.

Start free trial

More electrical calculators