Voltage drop calculator
Voltage drop in volts and per cent for copper or aluminum conductors, checked against the Canadian Electrical Code 3% and 5% limits, with the smallest size that passes.
Your job
For a 120 V load on a 120/240 V system choose the 120 V option.
Used only for the DC system.
Aluminum starts at 12 AWG; a smaller choice is raised to 12. Resistance is computed from the size.
Run length from source to load, one way. The calculator doubles it for the return path.
Use 1.00 for resistive loads such as heaters and lighting; 0.8 to 0.9 for motors.
Picks the typical reactance estimate used for AC circuits when no reactance is entered below.
AC only, and it matters when the power factor is below 1. Enter the figure from the conductor or cable maker. Leave at 0 to use a typical estimate: 0.14 ohm/km for non-metallic and aluminum wiring, 0.17 ohm/km for steel.
Rule 8-102 allows 3% in either one.
Feeder drop ahead of a branch circuit, so the 5% total can be checked.
Answer
- Voltage drop
- 5.82 V (4.85%)
- Over the 3% limit
- Fail
- Smallest size within the limit
- 8 AWG
- Total with upstream drop
- 4.85% (limit 5%)
- Voltage at the load
- 114.2 V of 120 V
- Voltage drop of 4.85% is over the 3% limit for a branch (Rule 8-102).
Method: CEC 2024 Rule 8-102 (voltage drop limits: 3% in a feeder or branch circuit, 5% total); Resistance is computed, not looked up: copper 0.017241 and aluminum 0.028264 ohm.mm2/m at 20 °C, temperature coefficients 0.00393 and 0.00403 per °C, worked at 75 °C, with a stranding factor of 1.02. AWG area from d = 0.127 mm x 92^((36-n)/39); kcmil x 0.5067 mm2; Reactance: typical reactance estimate 0.14 ohm/km (not entered); Method: drop = 2 x I x L x Z (single-phase, DC) or 1.732 x I x L x Z (three-phase), with Z = R cos(phi) + X sin(phi); Voltage drop only: check the conductor ampacity separately with the conductor check calculator; Check against the CEC edition and amendments your province adopts; confirm with the authority having jurisdiction.
Estimating aid based on a summary of the CEC. Provinces adopt different editions and amendments. Confirm with the authority having jurisdiction, and the engineer of record where one is involved.
Priced takeoff
- RW90 stranded copper building wire 12 AWG$64.2060 m at $1.070.84 h
- Materials
- $64.20
- Labour, 0.84 h at $99.00
- $83.16
- Your cost, before markup and tax
- $147.36
Reference prices are dated baselines (2026-11) for Ontario. Confirm them with your supplier. In TradeQuote PRO your own saved prices replace these.
How it works
You enter 12 inputs. The calculator returns the quantities, rounds them up the way the material is sold, and lists the takeoff so it can be priced.
- System. For a 120 V load on a 120/240 V system choose the 120 V option.
- DC system voltage (V). Used only for the DC system.
- Conductor material.
- Conductor size. Aluminum starts at 12 AWG; a smaller choice is raised to 12. Resistance is computed from the size.
- One-way length. Run length from source to load, one way. The calculator doubles it for the return path.
- Length unit.
- Load current (A).
- Power factor. Use 1.00 for resistive loads such as heaters and lighting; 0.8 to 0.9 for motors.
- Wiring method. Picks the typical reactance estimate used for AC circuits when no reactance is entered below.
- Reactance (optional) (ohm/km). AC only, and it matters when the power factor is below 1. Enter the figure from the conductor or cable maker. Leave at 0 to use a typical estimate: 0.14 ohm/km for non-metallic and aluminum wiring, 0.17 ohm/km for steel.
- Circuit type. Rule 8-102 allows 3% in either one.
- Drop already used upstream (%). Feeder drop ahead of a branch circuit, so the 5% total can be checked.
The method
- CEC 2024 Rule 8-102 (voltage drop limits: 3% in a feeder or branch circuit, 5% total)
- Resistance is computed, not looked up: copper 0.017241 and aluminum 0.028264 ohm.mm2/m at 20 °C, temperature coefficients 0.00393 and 0.00403 per °C, worked at 75 °C, with a stranding factor of 1.02. AWG area from d = 0.127 mm x 92^((36-n)/39); kcmil x 0.5067 mm2
- Reactance: typical reactance estimate 0.14 ohm/km (not entered)
- Method: drop = 2 x I x L x Z (single-phase, DC) or 1.732 x I x L x Z (three-phase), with Z = R cos(phi) + X sin(phi)
- Voltage drop only: check the conductor ampacity separately with the conductor check calculator
- Check against the CEC edition and amendments your province adopts; confirm with the authority having jurisdiction.
Check results against the code and manufacturer data that apply to your job. Prices are dated baselines to confirm with a supplier.
Add this to a real estimate in TradeQuote PRO
The takeoff lands as estimate lines with your prices, markup and tax, then becomes a proposal the client signs.
More electrical calculators
- Conductor check (ampacity)Checks a conductor against a load: required ampacity with the continuous-load factor against the ampacity you read from your code book, corrected for ambient and conductor count, with pass or fail.
- Conduit fill calculatorConduit fill from the conductor and conduit diameters you enter, checked against the 53/31/40 per cent fill limits, with conduit, couplings, connectors and wire for the takeoff.
- Box fill calculatorAdds up the applicable box-fill allowances you enter for conductors, devices and clamps, and compares the total with the volume marked on the box.
- Motor circuit calculatorChecks motor-circuit values using the full-load current, protection percentage and other values you enter from the electrical code adopted in your jurisdiction.